Current standards for capacitors are defined so that capacitors can withstand a permanent overcurrent of 30%. These standards also permit a maximum tolerance of 10% on the nominal capacitance. Cables must therefore the sized at least for: I cable = 1.3 × 1.1 (I nominal capacitor) i.e. I cable = 1.43 × I nominal. Go back to capacitors ...